WebIRC Quick Reference Links; Blog; Make A Donation; Calculators; Join/Login ... Fuel/Gas Piping. Fuel Gas Piping Bonding of Gas Piping. Section G2411 IRC. G2411.1 (310.1) General Bonding (not including CSST) G2411.1.1 (310.1.1) CSST Bonding Requirements. Sizing. Section G2413 IRC. This section also includes multiple charts to size different ... WebJul 6, 2024 · 7.12.2.1. The bonding jumper shall connect to a metallic pipe, pipe fitting, or CSST fitting. 7.12.2.2. The bonding jumper shall not be smaller than 6 AWG copper wire or equivalent. 7.12.2.3*. The length of the jumper between the connection to the gas piping system and the grounding electrode system shall not exceed 75 ft (22 m).
Fuel/Gas Piping Building Intelligence Center
WebJan 31, 2024 · The IRC/2009 and IFGC/2009 state: “G2411.1.1 (310.1.1) CSST. Corrugated stainless steel tubing (CSST) gas piping systems shall be bonded to the electrical service grounding electrode system at the point where the gas service enters the building. The bonding jumper shall be not smaller than 6 AWG copper wire or equivalent.” WebSection G2411.2 (310.2) CSST, of the IRC, is hereby amended by deleting said section (not including subsections) and inserting in lieu thereof the following: Section G2411.2 (310.2) Existing CSST - Bonding Required Where alterations, repairs or additions requiring a permit occur, CSST shall be bonded in accordance with the Ankeny Fuel Gas Code ... imdb a touch of sin
CSST Gas Lines – Installation and Bonding Requirements
WebThe bonding clamp shall be attached to a segment of metallic fuel gas pipe which (a) is a component of the gas piping system, (b) is electrically continuous with all CSST components of the gas piping system, (c) is made of steel or wrought-iron, (d) complies with Section G2414.4.2 of this code and with all other applicable provisions of Section ... WebThe 2012 code, prior to any amendments, required the bonding to occur where the gas service entered the building. In the 2024 code, several sections were added under the … WebMar 1, 2024 · What we are learning now is that installations of CSST gas pipe need an additional bonding point to the home’s system grounding for fire safety. There have been house fires blamed on faulty CSST … imdb atlas shrugged part 2